GD310-UL series VFD
Function parameter
-53-
Function
code
Name
Description
Default
value
Modify
P02.23
Back EMF
constant of
SM 1
When P00.15=2, the set value of P02.23 cannot be
updated by autotuning, please count according to the
following method.
The counter-electromotive force constant can be
counted according to the parameters on the name
plate of the motor. There are three ways to count:
1.
If
the
name
plate
designate
the
counter-electromotive force constant Ke, then:
E=(Ke*n
N
*2π)/ 60
2.
If
the
name
plate
designate
the
counter-electromotive
force
constant
E’(V/1000r/min), then:
E=E’*n
N
/1000
3. If the name plate does not designate the above
parameters, then:
E=P/√3*I
In the above formulas: n
N
is the rated rotation speed,
P is the rated power and I is the rated current.
Setting range: 0
–10000
300
○
P02.24
Reserved
P02.25
Reserved
P02.26
Motor 1
overload
protection
0: No protection
1: Common motor (with low speed compensation).
Because the heat-releasing effect of the common
motors will be weakened, the corresponding electric
heat protection will be adjusted properly. The low
speed compensation characteristic mentioned here
means reducing the threshold of the overload
protection of the motor whose running frequency is
below 30Hz.
2: Variable frequency motor (without low speed
compensation) Because the heat-releasing effect of
the specific motors won’t be impacted by the rotation
speed, it is not necessary to adjust the protection
value during low-speed running.
2
◎
P02.27
Motor 1
overload
protection
Times of motor overload M = Iout/(In*K)
In is the rated current of the motor, Iout is the output
current of the VFD and K is the motor protection
100.0%
○