GD310-UL series VFD
Function parameter
-73-
Function
code
Name
Description
Default
value
Modify
12: AI3 input value
13: High speed pulse HDI input value
14: MODBUS communication set value 1
15: MODBUS communication set value 2
16: PROFIBUS/CANopen communication set value 1
17: PROFIBUS/CANopen communication set value 2
18: Ethernet communication set value 1
19: Ethernet communication set value 2
20
–21: Reserved
22: Torque current (relative to 3 times the rated
current of the motor)
23: Ramp reference frequency (with sign)
24
–30: Reserved
P06.17
Lower output
limit of AO1
The above function codes define the relative
relationship between the output value and analog
output. When the output value exceeds the range of
set maximum or minimum output, it will count
according to the low-limit or upper-limit output.
When the analog output is current output, 1mA
equals to 0.5V.
In different cases, the corresponding analog output
of 100% of the output value is different. For detailed
information, please refer to analog output
instructions in
Chapter 7
.
10V (20mA)
0.0%
100.0%
AO
Setting range of P06.18: 0.00V
–10.00V
Setting range of P06.19: P06.17
–100.0%
Setting range of P06.20: 0.00V
–10.00V
Setting range of P06.21: 0.000s
–10.000s
Setting range of P06.22: -100.0%
–P06.24
Setting range of P06.23: 0.00V
–10.00V
Setting range of P06.24: P06.22
–100.0%
0.0%
○
P06.18
Corresponding
AO1 output of
lower limit
0.00V
○
P06.19
Upper output
limit of AO1
100.0%
○
P06.20
Corresponding
AO1 output of
upper limit
10.00V
○
P06.21
AO1 output
filter time
0.000s
○
P06.22
Lower output
limit of AO2
0.0%
○
P06.23
Corresponding
AO2 output of
lower limit
0.00V
○
P06.24
Upper output
limit of AO2
100.0%
○
P06.25
Corresponding
AO2 output of
upper limit
10.00V
○
P06.26
AO2 output
filter time
0.000s
○