GD310-UL series VFD
Installation guidelines
-22-
4.3 Standard wiring
4.3.1 Connection diagram of main circuit
Connection diagram of main circuit for the VFDs of AC 3PH 380V
–480V
3-PH power supply
50/60Hz
Braking resistor
Fuse
Input
reactor
Input
filter
Output
reactor
Output
filter
VFD
Figure 4-7 Connection diagram of main circuit for the VFD of
220V
≤15kW; 460V G-type≤30kW, P-type≤37kW
3-PH power supply
50/60Hz
Fuse
Input
reactor
Input
filter
DC reactor
Braking unit
Braking resistor
Output
reactor
Output
filter
VFD
Figure 4-8 Connection diagram of main circuit for the VFDs of
220V 18.5
–55kW; 460V G-type≥37kW, P-type≥45kW
Note:
The fuse, DC reactor, braking unit, braking resistor, input reactor, input filter, output reactor,
output filter are optional parts. Please refer to Peripheral options and parts for detailed
information.
P1
and
(+)
are short circuited in factory for the VFDs of 220V (
≥18.5kW), 460V (G-type≥37kW,
P-type
≥45kW), if need to connect with the DC rector, please remove the jumper between
P1
and
(+)
.
Remove the yellow warning labels of
PB
,
(+)
and
(-)
on the terminals before connecting the
braking resistor; otherwise, poor connection may occur.
3-PH power supply
50/60Hz
Fuse
Input
reactor
Input
filter
DC reactor
Braking unit
Braking resistor
Output
reactor
Output
filter
Figure 4-9 Connection diagram of main circuit for the VFDs of 575V
Содержание GD310-011P-4-UL