-152-
Function
code
Name
Description
Default
value
36: Shift the command to the keypad
37: Shift the command to the terminals
38: Shift the command to the communication
39: Pre-magnetized command
40: Consumption power clear
41: Consumption power holding
42
–63: Reserved
61: PID pole switching
62
–63: Reserved
P05.10
Polarity selection of input
terminal
0x000
–0x1FF
0x000
P05.11
ON-OFF filter time
0.000
–1.000s
0.010s
P05.12
Virtual terminals setting
0x000
–0x1FF (0: Disabled, 1: Enabled )
BIT0: S1
virtual terminal
BIT1: S2
virtual terminal
BIT2: S3
virtual terminal
BIT3: S4
virtual terminal
BIT4: S5
virtual terminal
BIT5: S6
virtual terminal
BIT6: S7
virtual terminal
BIT7: S8
virtual terminal
BIT8: HDI
virtual terminal
0x000
P05.13
Terminals control running
mode
0: 2-wire control 1
1: 2-wire control 2
2: 3-wire control 1
3: 3-wire control 2
0
P05.14 Switch-on delay of S1 terminal 0.000
–50.000s
0.000s
P05.15 Switch-off delay of S1 terminal 0.000
–50.000s
0.000s
P05.16 Switch-on delay of S2 terminal 0.000
–50.000s
0.000s
P05.17 Switch-off delay of S2 terminal 0.000
–50.000s
0.000s
P05.18 Switch-on delay of S3 terminal 0.000
–50.000s
0.000s
P05.19 Switch-off delay of S3 terminal 0.000
–50.000s
0.000s
P05.20 Switch-on delay of S4 terminal 0.000
–50.000s
0.000s
P05.21 Switch-off delay of S4 terminal 0.000
–50.000s
0.000s
P05.22 Switch-on delay of S5 terminal 0.000
–50.000s
0.000s
P05.23 Switch-off delay of S5 terminal 0.000
–50.000s
0.000s
P05.24 Switch-on delay of S6 terminal 0.000
–50.000s
0.000s
Содержание GD310-011P-4-UL