GD310-UL series VFD
Basic operation instruction
-150-
Set
value
Function
Instructions
33
Frequency
increasing/decreasing
setting temporal clear
When the terminal closes, the frequency set by UP/DOWN
can be cleared. All set frequency will be restored into the
given frequency by the frequency command channel and the
frequency will come back to the value after the frequency
increasing or decreasing.
34
DC braking
The VFD will begin DC braking after the valid command.
35
Switch between motor1 and
motor2
Motor-shifting can be controlled after the terminal is valid.
36
Switch commands to
keypad
After the function terminal become valid, the running
command channel will be shifted into keypad running
command channel and the running command channel will
come back to the original state if function terminal is invalid.
37
Switch commands to
terminals
After the function terminal become valid, the running
command channel will be shifted into terminal running
command channel and the running command channel will
come back to the original state if function terminal is invalid.
38
Switch commands to
communication
After the function terminal become valid, the running
command channel will be shifted into communication running
command channel and the running command channel will
come back to the original state if function terminal is invalid.
39
Pre-excitation commands
Perform pre-exciting if the terminal is valid until the terminal is
invalid.
40
Power consumption clear
The power consumption will be cleared after the command is
valid.
41
Power consumption
retention
If the command is valid, the current running of the VFD will
not affect its power consumption.
42
–60
Reserved
61
PID pole switching
Switch the output pole of PID and be used with P09.03
62
–63
Reserved
Related parameters list:
Function
code
Name
Description
Default
value
P05.00
HDI input selection
0: High pulse input
1: Digital input
0
P05.01 S1 terminals function selection 0: No function
1: Forward rotation operation
2: Reverse rotation operation
1
P05.02 S2 terminals function selection
4
P05.03 S3 terminals function selection
7