GD310-UL series VFD
Function parameter
-65-
Function
code
Name
Description
Default
value
Modify
the input
terminals
Set the bit to 0, the input terminal is anode.
Set the bit to 1, the input terminal is cathode.
BIT0
BIT1
BIT2
BIT3
BIT4
S1
S2
S3
S4
S5
BIT5
BIT6
BIT7
BIT8
S6
S7
S8
HDI
The setting range: 0x000
–0x1FF
P05.11
ON-OFF filter
time
Set the sample filter time of S1
–S8 and HDI
terminals. If the interference is strong, increase the
parameter to avoid the disoperation.
0.000
–1.000s
0.010s
○
P05.12
Virtual
terminals
setting
0x000
–0x1FF (0: Disabled, 1: Enabled )
BIT0: S1
virtual terminal
BIT1: S2
virtual terminal
BIT2: S3
virtual terminal
BIT3: S4
virtual terminal
BIT4: S5
virtual terminal
BIT5: S6
virtual terminal
BIT6: S7
virtual terminal
BIT7: S8
virtual terminal
BIT8: HDI
virtual terminal
0x000
◎
P05.13
Terminals
control running
mode
Set the operation mode of the terminals control
0: 2-wire control 1, comply the enable with the
direction. This mode is widely used. It determines the
rotation direction by the defined FWD and REV
terminals command.
FWD
REV
COM
K1
K2
Running
command
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stop
Hold
FWD
running
REV
running
1: 2-wire control 2; Separate the enable from the
direction. FWD defined by this mode is the enabling
ones. The direction depends on the state of the
defined REV.
0
◎