GD310-UL series VFD
Function parameter
-85-
Function
code
Name
Description
Default
value
Modify
Y
RO1, RO2
,
Output frequency
The set
frequency
Detecting
range
T
T
The setting range: 0.00Hz
–P00.03 (the max
frequency)
P08.37
Energy
braking enable
This parameter is used to control the internal braking
pipe inside the VFD.
0: Disable
1: Enable
Note
: Only applied to internal braking pipe.
0
○
P08.38
Threshold
voltage
After setting the original bus voltage to brake the
energy, adjust the voltage appropriately to brake the
load. The factory changes with the voltage level.
The setting range: 200.0
–2000.0V
In order to prevent customers set the value is too
large, it is recommended setting range:
Voltage
220V
460V
575V
Range 360-390V 715
–780V 950-1050V
220V
voltage:
380.0V
○
460V
voltage:
740.0V
575V
voltage:
1000.0V
P08.39
Cooling fan
running mode
0: Normal mode
1: The fan keeps running after power on
0
○
P08.40
PWM
selection
0x00
–0x21
LED ones: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
LED tens: low-speed carrier frequency limit mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at low
speed
1: Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k at low
speed
2: No limit
01
◎