GD310-UL series VFD
Basic operation instruction
-132-
Related parameters list:
Function
code
Name
Description
Default value
P00.01
Run command channel
0: Keypad running command
1: Terminal running command
channel (“LOCAL/REMOT”
flickering)
2: Communication running command
channel
(“LOCAL/REMOT” on);
0
P00.15
Motor parameter autotuning
0: No operation
1: Rotating autotuning
2: Static autotuning 1 (autotune
totally)
3: Static autotuning 2 (autotune part
parameters)
0
P02.00
Motor type 1
0: Asynchronous motor
1: Synchronous motor
0
P02.01
Rated power of AM 1
0.1
–3000.0kW
Depend on model
P02.02
Rated frequency of AM 1
0.01Hz
–P00.03 (the max frequency)
60.00Hz
P02.03
Rated speed of AM 1
1
–36000rpm
Depend on model
P02.04
Rated voltage of AM 1
0
–1200V
Depend on model
P02.05
Rated current of AM 1
0.8
–6000.0A
Depend on model
P02.06
Stator resistor of AM 1
0.001
–65.535Ω
Depend on model
P02.07
Rotor resistor of AM 1
0.001
–65.535Ω
Depend on model
P02.08
Leakage inductance of AM 1 0.1
–6553.5mH
Depend on model
P02.09
Mutual inductance of AM 1 0.1
–6553.5mH
Depend on model
P02.10
Non-load current of AM1
0.1
–6553.5A
Depend on model
P02.15
Rated power of SM 1
0.1
–3000.0kW
Depend on model
P02.16
Rated frequency of SM 1
0.01Hz
–P00.03 (the max frequency)
60.00Hz
P02.17
Number of poles pairs for SM
1
1
–50
2
P02.18
Rated voltage of SM 1
0
–1200V
Depend on model
P02.19
Rated current of SM 1
0.8
–6000.0A
Depend on model
P02.20
Stator resistor of SM 1
0.001
–65.535Ω
Depend on model
P02.21
Direct axis inductance of SM
1
0.01
–655.35mH
Depend on model
P02.22
Quadrature axis inductance
of SM 1
0.01
–655.35mH
Depend on model
P02.23
Back EMF constant of SM 1 0
–10000
300
Содержание GD310-011P-4-UL