GD310-UL series VFD
Basic operation instruction
-151-
Function
code
Name
Description
Default
value
P05.04 S4 terminals function selection 3: 3-wire control operation
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Operation pause
9: External fault input
10: Increasing frequency setting (UP)
11: Decreasing frequency setting (DOWN)
12: Frequency setting clear
13: Shift between A setting and B setting
14: Shift between combination setting and A
setting
15: Shift between combination setting and B
setting
16: Multi-step speed terminal 1
17: Multi-step speed terminal 2
18: Multi-step speed terminal 3
19: Multi- step speed terminal 4
20: Multi- step speed pause
21: ACC/DEC time 1
22: ACC/DEC time 2
23: Simple PLC stop reset
24: Simple PLC pause
25: PID control pause
26: Traverse Pause (stop at present
frequency)
27: Traverse reset (return to center
frequency)
28: Counter reset
29: Torque control disabling
30: ACC/DEC disabling
31: Counter trigging
32: Length reset
33: Cancel the frequency change setting
temporarily
34: DC brake
35: Shift the motor 1 into motor 2
0
P05.05 S5 terminals function selection
0
P05.06 S6 terminals function selection
0
P05.07 S7 terminals function selection
0
P05.08 S8 terminals function selection
0
P05.09 HDI terminal function selection
0