GD310-UL series VFD
Peripheral options and parts
-244-
Model
Recommended cable size
(mm
2
)
Required torque
(in-lbs)
Wire
connector
(##)
R,S,T; U,V,W;
P1, (+), PB, (-)
PE
R,S,T; U,V,W;
P1, (+); PB, (-)
PE
GD310-030P-4-UL
3AWG
8AWG
25.5
18
Required
GD310-037P-4-UL
3AWG
6AWG
25.5
18
Required
GD310-045P-4-UL
2/0
6AWG
25.5
75
Required
GD310-055P-4-UL
2/0
6AWG
25.5
75
Required
GD310-075P-4-UL
3/0AWG
1 AWG
60 or 80 $$
10
Required
GD310-090P-4-UL
GD310-110P-4-UL
1/0 AWG x 2
1 AWG
90
10
Required
GD310-132P-4-UL
350kcmil x 2
1 AWG
338.2
338.2
Optional
GD310-160P-4-UL
Optional
GD310-185P-4-UL
Optional
GD310-200P-4-UL
Optional
GD310-220P-4-UL
Optional
GD310-250P-4-UL
350kcmil*3
2/0AWG
338.2
338.2
Optional
GD310-280P-4-UL
Optional
GD310-315P-4-UL
Optional
GD310-350P-4-UL
Optional
GD310-400P-4-UL
350kcmil*4
4/0AWG
338.2
338.2
Optional
GD310-500P-4-UL
Optional
GD310-018G-6-UL
4AWG
8AWG
22 or 60 or
49.5 @@
10
Required
GD310-022G-6-UL
GD310-030G-6-UL
GD310-037G-6-UL
GD310-045G-6-UL
3/0AWG
2AWG
60
10
Required
GD310-055G-6-UL
GD310-075G-6-UL
GD310-090G-6 -UL
GD310-110G-6-UL
Control terminal block
26-14 (Str/Sol)
AWG
/
4.5
/
Optional
Note
:
1. It is appropriate to use the recommended cable size under 40°C and rated current. The wiring
distance should be no more than 100m.