GD310-UL series VFD
Basic operation instruction
-170-
Function
code
Name
Description
Default
value
19: Current detection fault (ItE)
20: Motor autotuning fault (tE)
21: EEPROM operation fault (EEP)
22: PID feedback offline fault (PIDE)
23: Braking unit fault (bCE)
24: Running time reached (END)
25: Electronic overload (OL3)
26: Keypad communication fault (PCE)
27: Parameter uploading fault (UPE)
28: Parameter downloading fault (DNE)
29: PROFIBUS communication fault
(E-DP)
30: Ethernet communication fault (E-NET)
31: CANopen communication fault
(E-CAN)
32: To-ground short-circuit fault 1 (ETH1)
33: To-ground short-circuit fault 2 (ETH2)
34: Speed deviation fault (dEu)
35: Mal-adjustment (STo)
36: Underload fault (LL)
P07.33
Running frequency at present fault
0.00Hz
P07.34
Ramp reference frequency at present fault
0.00Hz
P07.35
Output voltage at the present fault
0V
P07.36
Output current at present fault
0.0A
P07.37
Bus voltage at present fault
0.0V
P07.38
The max temperature at present fault
0.0°C
P07.39
Input terminals state at present fault
0
P07.40
Output terminals state at present fault
0
P07.41
Running frequency at the last fault
0.00Hz
P07.42
Ramp reference frequency at the last fault
0.00Hz
P07.43
Output voltage at the last fault
0V
P07.44
The output current at the last fault
0.0A
P07.45
Bus voltage at the last fault
0.0V
P07.46
The max temperature at the last fault
0.0°C
P07.47
Input terminals state at the last fault
0
P07.48
Output terminals state at the last fault
0
P07.49
Running frequency at the last but one fault
0.00Hz
P07.50
Output voltage at the last but one faults
0.00Hz