GD310-UL series VFD
Basic operation instruction
-143-
Function
code
Name
Description
Default
value
P05.41
AI2 input filter time
0.000s
–10.000s
0.100s
P05.42
Lower limit of AI3
-10.00V
–P05.44
-10.00V
P05.43
Corresponding setting of the lower
limit of AI3
-100.0%
–100.0%
-100.0%
P05.44
Middle value of AI3
P05.42
–P05.46
0.00V
P05.45
Corresponding middle setting of AI3 -100.0%
–100.0%
0.0%
P05.46
Upper limit of AI3
P05.44
–10.00V
10.00V
P05.47
Corresponding setting of
the upper limit of AI3
-100.0%
–100.0%
100.0%
P05.48
AI3 input filter time
0.000s
–10.000s
0.100s
P05.49
HDI high-speed pulse input function
selection
0: Frequency setting input,
frequency setting source
1: Counter input, high-speed pulse
counter input terminals
2: Length counting input, length
counter input terminals
0
P05.50
Lower limit frequency of HDI
0.000kHz
–P05.52
0.000kHz
P05.51
Corresponding setting of HDI low
frequency setting
-100.0%
–100.0%
0.0%
P05.52
Upper limit frequency of HDI
P05.50
–50.000kHz
50.000kHz
P05.53
Corresponding setting of upper limit
frequency of HDI
-100.0%
–100.0%
100.0%
P05.54
HDI frequency input filter time
0.000s
–10.000s
0.100s
7.10 Analog output
Goodrive310-UL series VFDs have 2 analog output terminals (0
–10V or 0–20mA) and 1 high speed
pulse output terminal. Analog output signal can be filtered and the maximum and minimum values can
be adjusted. The analog output signals can be proportional to motor speed, output frequency, output
current, motor torque, motor power, etc.