Function
code
Name
Description
Default
value
Modify
P01.04
The braking
time before
starting
0, the DC braking is invalid.
The stronger the braking current, the bigger the
braking power. The DC braking current before
starting means the percentage of the rated output
current of the VFD.
Setting range of P01.03: 0.0
–100.0%
Setting range of P01.04: 0.00
–50.00s
0.00s
◎
P01.05
ACC/DEC
selection
The changing mode of the frequency during start-up
and running.
0: Linear type
The output frequency increases or decreases
linearly.
fmax
Output frequency
t
1
t
2
t
1: Reserved
0
◎
P01.06
Reserved
◎
P01.07
◎
P01.08
Stop mode
0: Decelerate to stop: after the stop command
becomes valid, the VFD decelerates to decrease the
output frequency during the set time. When the
frequency decreases to P01.15, the VFD stops.
1: Coast to stop: after the stop command becomes
valid, the VFD ceases the output immediately. And
the load coasts to stop at the mechanical inertia.
0
○
P01.09
Starting
frequency of
DC braking
The starting frequency of stop braking: the VFD will
carry on stop DC braking when the frequency is
arrived during the procedure of decelerating to stop.
The waiting time of stop braking: before the stop DC
braking, the VFD will close output and begin to carry
on the DC braking after the waiting time. This
function is used to avoid the overcurrent fault caused
by DC braking when the speed is too high.
Stop DC braking current: the DC brake added. The
stronger the current, the bigger the DC braking
effect.
0.00Hz
○
P01.10
Waiting time of
DC braking
0.00s
○
P01.11
DC braking
current
0.0%
○
P01.12
DC braking
time
0.00s
○