GD310-UL series VFD
Function parameter
-92-
Function
code
Name
Description
Default
value
Modify
impact of continuous working and the integration will
change with the trend.
1: Stop integral adjustment when the frequency
achieves the upper and low limit. If the integration
keeps stable, and the trend between the reference
and the feedback changes, the integration will
change with the trend quickly.
LED tens: P00.08 is 0
0: The same with the setting direction; if the output of
PID adjustment is different from the current running
direction, the internal will output 0 forcedly.
1: Opposite to the setting direction
LED hundreds: P00.08 is 0
0: Limit to the maximum frequency
1: Limit to frequency A
LED thousands:
0: A+B frequency, the buffer of A frequency is invalid
1: A+B frequency, the buffer of A frequency is valid
ACC/DEC is determined by ACC time 4 of P08.04
P09.14
Proportional
gain at low
frequency (Kp)
0.00
–100.00
1.00
○
P09.15
PID command
of ACC/DEC
time
0.0
–1000.0s
0.0s
○
P09.16
PID output
filter time
0.000
–10.000s
0.000s
○
P10 Group Simple PLC and multi-step speed control
Function
code
Name
Description
Default
value
Modify
P10.00
Simple PLC
0: Stop after running once. The VFD has to be
commanded again after finishing a cycle.
1: Run at the final value after running once. After
finish a signal, the VFD will keep the running
frequency and direction of the last run.
2: Cycle running. The VFD will keep on running until
receiving a stop command. And then, the system will
stop.
0
○