GD310-UL series VFD
Fault tracking
-173-
Fault
code
Fault type
Cause
Solution
OUt3
[3] IGBT W
phase
protection
driving wires is not good
The grounding is not good
equipment
OC1
[4] Overcurrent
during
acceleration
The acceleration or
deceleration is too fast
The voltage of the grid is too
low
The power of the VFD is too
low
The load transients or is
abnormal
The grounding is short
circuited or the output is
phase loss
There is strong external
interference
The overvoltage stall
protection is not open
Increase the acc. time
Check the input power
Select the VFD with a larger
power
Check if the load is short circuited
(the grounding short circuited or
the wire short circuited) or the
rotation is not smooth
Check the output configuration.
Check if there is strong
interference
Check the setting of related
function codes
OC2
[5] Overcurrent
during
deceleration
OC3
[6] Overcurrent
during constant
speed running
OV1
[7] Overvoltage
during
acceleration
The input voltage is
abnormal
There is large energy
feedback
No braking components
Braking energy is not open
Check the input power
Check if the DEC time of the load
is too short or the VFD starts
during the rotation of the motor or
it needs to increase the energy
consumption components
Install the braking components
Check the setting of related
function codes
OV2
[8] Overvoltage
during
deceleration
OV3
[9] Overvoltage
during constant
speed running
UV
[10] Bus
undervoltage
The voltage of the power
supply is too low
The overvoltage stall
protection is not open
Check the input power of the
supply line
Check the setting of related
function codes
OL1
[11] Motor
overload
The voltage of the power
supply is too low
The motor setting rated
current is incorrect
The motor stall or load
transients is too strong
Check the power of the supply
line
Reset the rated current of the
motor
Check the load and adjust the
torque lift