GD310-UL series VFD
Basic operation instruction
-118-
Function
code
Name
Description
Default
value
P07.02
QUICK/JOG function
selection
0: No function
1: Jogging
2: Shift the display state by the shifting key
3: Shift between forward rotations and reverse
rotations
4: Clear UP/DOWN settings
5: Coast to stop
6: Shift the given manner of running commands
7: Quick commissioning mode (committee
according to the non-factory parameter)
1
7.3 Vector control
Because asynchronous motors have the characteristics of high stage, nonlinear, strong coupling and
various variables, the actual control of the asynchronous motor is very difficult. Vector control is
mainly used to settle this problem with the theme of that divide the stator current vector into exciting
current (the current heft generating internal magnetic field of the motor) and torque current (the
current heft generating torque) by controlling and measuring the stator current vector according to the
principles of beamed magnetic field to control the range and phase of these two hefts. This method
can realize the decoupling of exciting current and torque current to adjust the high performance of
asynchronous motors.
Goodrive310-UL series VFDs are embedded with speed sensor-less vector control calculation for
driving both asynchronous motors and synchronous motors. Because the core calculation of vector
control is based on exact motor parameter models, the accuracy of motor parameter will impact on
the performance of vector control. It is recommended to input the motor parameters and carry out
autotune before vector running.
Because the vector control calculation is very complicated, high technical theory is needed for the
user during internal autotune. It is recommended to use the specific function parameters in vector
control with cautions.