Function parameter
-49-
Function
code
Name
Description
Default
value
Modify
P01.17
Detection time
of feedback
speed
If set P01.16 to 1, the feedback frequency is less
than or equal to P01.15 and detect in the set time of
P01.17, the VFD will stop; otherwise the VFD will
stop after the set time of P01.17.
T
Stop speed
A
Ramp reference
frequency
Output frequency
Frequency
P0124
.
P0117
.
B
C
Setting range: 0.00
–100.00s (only valid when
P01.16=1)
0.50s
◎
P01.18
Terminal
running
protection
when
powering on
When the running commands are controlled by the
terminal, the system will detect the state of the
running terminal during powering on.
0: The terminal running command is invalid when
powering on. Even the running command is detected
to be valid during powering on, the VFD
won’t run
and the system keeps in the protection state until the
running command is canceled and enabled again.
1: The terminal running command is valid when
powering on. If the running command is detected to
be valid during powering on, the system will start the
VFD automatically after the initialization.
Note
: this function should be selected with cautions,
or serious result may follow.
0
○
P01.19
Action if
running
frequency<
lower limit
frequency
(valid >0)
This function code determines the running state of
the VFD when the set frequency is lower than the
lower-limit one.
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
The VFD will coast to stop when the set frequency is
lower than the lower-limit one. If the set frequency is
above the lower limit one again and it lasts for the
time set by P01.20, the VFD will come back to the
running state automatically.
0
◎