code
Name
Description
Default
value
Modify
2: Odd check (O,8,1) for RTU
3: No check (N,8,2) for RTU
4: Even check (E,8,2) for RTU
5: Odd check (O,8,2) for RTU
P14.03
Answer
delay
0
–200ms
The interval time when the drive receives the data
and sent it to the upper monitor. If the answer delay
is shorter than the system processing time, then the
answer delay time is the system processing time, if
the answer delay is longer than the system
processing time, then after the system deal with the
data, waits until achieving the answer delay time to
send the data to the upper monitor.
5
○
P14.04
Fault time of
communicatio
n overtime
0.0 (invalid), 0.1
–60.0s
When the function code is set as 0.0, the
communication overtime parameter is invalid.
When the function code is set as non-zero, if the
interval time between two communications exceeds
the communication overtime, the system will report
“485 communication faults” (CE).
Generally, set it as invalid; set the parameter in the
continuous
communication
to
monitor
the
communication state.
0.0s
○
P14.05
Transmission
fault
processing
0: Alarm and stop freely
1: No alarm and continue to run
2: No alarm and stop according to the stop mode
(only under the communication control)
3: No alarm and stop according to the stop mode
(under all control modes)
0
○
P14.06
Communica
-tion
processing
0x00
–0x11
LED ones:
0: Write with response: the VFD will respond to all
reading and writing commands of the upper monitor.
1: Write without response: the VFD only responds to
the reading command other than the writing
command of the drive. The communication efficiency
can be increased by this method.
LED tens:
0: Communication encrypting invalid
1: Communication encrypting valid
0x00
○