GD310-UL series VFD
Function parameter
-105-
Function
code
Name
Description
Default
value
Modify
P13.03
Source current
2
Source current is directional current of the magnetic
pole position. Source current 2 is valid under the
frequency point of current shifting. There is no need
to modify the value generally.
Setting range: 0.0%
–100.0% (rated motor current)
10.0%
○
P13.04
Shift
frequency of
source current
Valid frequency shifting point between source current
1 and current 2.
Setting range: 0.00Hz
–P00.03 (the max frequency)
10.00Hz
○
P13.05
Superposing
frequency
(reserved)
200
–1000Hz
500Hz
◎
P13.06
Pulse
superposing
voltage
0.0
–300.0% (rated voltage of the motor)
40.0%
◎
P13.07
Reserved
0
–65535
0
○
P13.08
Control
parameter 1
0
–65535
0
○
P13.09
Control
parameter 2
0
–655.35
2.00
○
P13.10
Reserved
0
–65535
0
○
P13.11
Maladjustment
detection time
Adjust the response of anti-maladjustment. Bigger
load inertia may increase the value, but the response
will be slower.
Setting range: 0.0
–10.0s
0.5s
○
P13.12
High
frequency
compensation
coefficient
When the motor speed is faster than the rated speed,
the parameter is valid, if vibration occurs to the
motor, please adjust the parameter.
Setting range: 0
–100.0%
0.0%
○
P13.13
Braking
current of
short-circuit
When P01.00=0 during the starting of the VFD, set
P13.14 to a non-zero value to enter the short circuit
braking.
When the running frequency is lower than P01.09
during the stopping of the VFD, set 13.15 to a
non-zero value to enter into stopping short circuited
braking and then carry out the DC braking at the time
set by P01.12 (refer to the instruction of
P01.09
–P01.12) .
Setting range of P13.13: 0.0
–150.0% (corresponding
0.0%
○
P13.14
Braking
retention time
before
starting
0.00s
○
P13.15
The braking
retention time
0.00s
○