GD310-UL series VFD
Basic operation instruction
-167-
Counting value
>P08.26
?
0
Counting value
>P08.25
?
Running
0
Digital output 18
Given counting value arrival
Digital output 17
Set counting value arrival
P05.00
(
HDI output type selection
)
P05.40
(
HDI input function selection
)
Terminal function 28
Counter reset
P08.26
Given counting value
P08.25
Set counting value
0
1
2
0
1
valid
invalid
Y
、
HDO
、
RO1
、
RO2
Y
、
HDO
、
RO1
、
RO2
Y
N
Y
N
P17.18
Counting value
Counter stop
Counting value
>P08.26
?
0
Counting value
>P08.25
?
Runnin
g
0
Digital output 18
Given counting value arrival
Digital output 17
Set counting value arrival
Terminal function
31
Counter triggering
Terminal function 28
Counter reset
P08.26
Given counting value
P08.25
Set counting value
0
1
Valid
Invalid
Y
N
Y
N
P17.18
Counting value
Given counting value arrival
output
Set counting value arrival output
Function
code
Name
Description
Default
value
P05.00
HDI input selection
0: High pulse input.
1: Digital input.
0
P05.40
Corresponding setting of
the upper limit of AI2
/
0
P05.01
–
P05.09
Digital input function
selection
28: Counter reset
31: Counter trigger
P06.01
–
P06.04
Digital output function
selection
17: Completion of simple PLC cycle
18: Setting count value arrival
P08.25
Setting counting value
P08.26
–65535
0
P08.26
Reference counting value 0
–P08.25
0
P17.18
Counting value
0
–65535
0
7.18 Fixed-length control
The VFDs support fixed-length control function which can input length counting pulse through HDI,
and then count the actual length according to the internal counting formula. If the actual length is
longer than or equal to the set length, the digital output terminal can output the length arrival pulse
signal of 200ms and the corresponding length will clear automatically.