GD310-UL series VFD
Function parameter
-48-
Function
code
Name
Description
Default
value
Modify
The braking time of stop braking: the retention time
of DC brake. If the time is 0, the DC brake is invalid.
The VFD will stop at the set deceleration time.
P01.23
ACC
Constant
speed
DEC
ON
T
P13.14
P01.04
P01.10
P13.15
P01.12
P01.09
Setting range of P01.09: 0.00Hz
–P00.03
Setting range of P01.10: 0.00
–50.00s
Setting range of P01.11: 0.0
–100.0% (corresponding
to the rated output current of the VFD)
Setting range of P01.12: 0.00
–50.00s
P01.13
Dead time of
FWD/REV
rotation
During the procedure of switching for/rev rotation, set
the threshold by P01.14, which is as the table below:
Output frequency
FWD
REV
T
Starting
frequency
Shift after the
zero frequency
Shift after the
starting frequency
Setting range: 0.0
–3600.0s
0.0s
○
P01.14
Shifting
between
FWD/REV
rotation
Set the threshold point of the VFD:
0: Switch after zero frequency
1: Switch after the starting frequency
2: Switch after the speed reach P01.15 and delay for
P01.24
0
◎
P01.15
Stopping
speed
0.00
–100.00Hz
0.50Hz
◎
P01.16
Detection of
stopping
speed
0: Detect according to speed setting (no stopping
delay)
1: Detect according to speed feedback (only valid for
vector control)
1
◎