GD310-UL series VFD
Function parameter
-77-
Function
code
Name
Description
Default
value
Modify
P07.07
Parameters for
stopping state
0x0000
–0xFFFF
BIT0: set frequency (Hz on, frequency flickering
slowly)
BIT1: bus voltage (V on)
BIT2: input terminals state
BIT3: output terminals state
BIT4: PID reference (% flickering)
BIT5: PID feedback value (% on)
BIT6: torque reference (% on)
BIT7: AI1 (V on)
BIT8: AI2 (V on)
BIT9: AI3 (V on)
BIT10: HDI frequency
BIT11: PLC and the current stage in multi-step speed
BIT12: pulse counters
BIT13: length value
BIT14: upper limit frequency (Hz on)
BIT15: reserved
0x00FF
○
P07.08
Frequency
coefficient
0.01
–10.00
Displayed frequency=running frequency* P07.08
1.00
○
P07.09
Rotation
speed
coefficient
0.1
–999.9%
Mechanical rotation speed =120*displayed running
frequency×P07.09/motor pole pairs
100.0%
○
P07.10
Linear speed
coefficient
0.1
–999.9%
Linear speed= Mechanical rotation speed×P07.10
1.0%
○
P07.11
Rectifier
bridge module
temperature
-20.0
–120.0°C
●
P07.12
Converter
module
temperature
-20.0
–120.0°C
●
P07.13
Software
version
1.00
–655.35
●
P07.14
Local
accumulative
running time
0
–65535h
●