GD310-UL series VFD
Function parameter
-87-
Function
code
Name
Description
Default
value
Modify
2: When the multi-step are priority, it is invalid to the
multi-step
LED hundreds: action selection when stop
0: Setting valid
1: Valid in the running, clear after stop
2: Valid in the running, clear after receiving the stop
commands
P08.45
UP terminals
frequency
changing ratio
0.01
–50.00Hz/s
0.50
Hz/s
○
P08.46
DOWN
terminals
frequency
changing ratio
0.01
–50.00 Hz/s
0.50
Hz/s
○
P08.47
Frequency
setting at
power loss
0x000
–0x111
LED ones: Action selection when power off.
0: Save when power off
1: Clear when power off
LED tens: Action selection when MODBUS set
frequency off
0: Save when power off
1: Clear when power off
LED hundreds: The action selection when other
frequency set frequency off
0: Save when power off
1: Clear when power off
0x000
○
P08.48
High bit of
initial power
consumption
This parameter is used to set the original value of the
power consumption.
The original value of the power consumption
=P08.48*1000+P08.49
Setting range of P08.48: 0
–59999 kWh (k)
Setting range of P08.49: 0.0
–999.9 kWh
0
○
P08.49
Low bit of
initial power
consumption
0.0
○
P08.50
Magnetic flux
braking
This function code is used to enable magnetic flux.
0: Invalid.
100
–150: The bigger the coefficient, the stronger the
braking is.
This VFD is used to increase the magnetic flux to
decelerate the motor. The energy generated by the
0
●