GD310-UL series VFD
Expansion card
-221-
State word (SW):
The first word of PZD response message is state word (SW) of VFD, the definition of state word is as
follows:
State Word (SW) of Goodrive310-UL
Bit
Name
Value
State/Description
0
–7
Run state byte
1
Forward running
2
Reverse running
3
The VFD stops
4
The VFD is in fault
5
The VFD is in POFF state
6
Pre-exciting state
8
Dc voltage establish
1
Running ready
0
The running preparation is not ready
9
–10
Motor group feedback
0
Motor 1 feedback
1
Motor 2 feedback
2
Motor 3 feedback
3
Motor 4 no feedback
11
Motor type feedback
1
Synchronous motor
0
Asynchronous motor
12
Overload alarm
1
Overload pre-alarm
0
Non-overload pre-alarm
13
Run/stop mode
0
Keypad control
1
Terminal control
14
2
Communication control
3
Reserved
15
Heartbeat feedback
1
Heartbeat feedback
0
No heartbeat feedback
Actual value (ACT):
From 2
nd
word to 12
th
of PZD task message is main set value ACT, main frequency set value is
offered by main setting signal source.
Actual value of Goodrive310-UL
Bit
Name
Function selection
PZD2 sending
0: Invalid
1: Running frequency (*100, Hz)
2: Set frequency (*100, Hz)
3: Bus voltage (*10, V)
0
PZD3 sending
0
PZD4 sending
0
PZD5 sending
0
Содержание GD310-011P-4-UL