GD310-UL series VFD
Communication protocol
-201-
Function
instruction
Address
definition
Data meaning instruction
R/W
attribute
2009H
Special control command word
Bit0
–1:=00: motor 1 =01: motor 2
=10: motor 3 =11: motor 4
Bit2:=1 torque control prohibit
=0: torque control prohibit invalid
Bit3:=1 power consumption clear
=0:no power consumption clear
Bit4:=1 pre-exciting enabling
=0: pre-exciting disabling
Bit5:=1 DC braking enabling
=0: DC braking disabling
R/W
200AH Virtual input terminal command , range: 0x000
–0x1FF
R/W
200BH Virtual output terminal command , range: 0x00
–0x0F
R/W
200CH
Voltage setting value (special for V/F separation)
(0
–1000, 1000 corresponds to the 100.0%)
R/W
200DH
AO output setting 1
(-1000
–1000, 1000 corresponds to 100.0%)
R/W
200EH
AO output setting 2
(-1000
–1000, 1000 corresponds to 100.0%)
R/W
SW 1 of the VFD
2100H
0001H: forward running
R
0002H: forward running
0003H: stop
0004H: fault
0005H: POFF state
0006H: pre-exciting state
SW 2 of the VFD
2101H
Bit0: =0:ready for operation =1:not ready for operation
Bi1
–2:=00:motor 1 =01:motor 2
=10:motor 3 =11:motor 4
Bit3: =0:asynchronous motor =1:synchronous motor
Bit4: =0:pre-alarm without overload =1:overload
pre-alarm
Bit5
– Bit6: =00: keypad control
=01: terminal control
=10: communication control
R
Fault code of the
VFD
2102H See the fault type instruction
R
Identifying code of
the VFD
2103H GD310-----0x010a
R