GD310-UL series VFD
Basic operation instruction
-149-
Set
value
Function
Instructions
16
Multi-step speed terminal 1 The 16 stage speeds can be set by the combination of digital
state of four terminals.
Note
: multi-step speed 1 is the low bit, multi-step speed 4 is
the high bit.
Multi-step
speed 4
Multi-step
speed 3
Multi-step
speed 2
Multi-step
speed 1
BIT3
BIT2
BIT1
BIT0
17
Multi-step speed terminal 2
18
Multi-step speed terminal 3
19
Multi-step speed terminal 4
20
Multi-step speed pause
Shield the multi-step speed selection terminal function to
keep the setting value at the current state.
21
ACC/DEC time selection 1 Select 4 ACC/DEC time by the combination of the 2
terminals.
Terminal
1
Terminal
2
ACC/DEC time
selection
Corresponding
parameter
OFF
OFF
ACC/DEC time 1 P00.11/P00.12
ON
OFF
ACC/DEC time 2 P08.00/P08.01
OFF
ON
ACC/DEC time 3 P08.02/P08.03
ON
ON
ACC/DEC time 4 P08.04/P08.05
22
ACC/DEC time selection 2
23
Simple PLC stop reset Restart simple PLC and clear the memory state of PLC.
24
Simple PLC pause
Program pause during PLC implement. Run at the current
speed stage. After cancel the function, simple PLC continues
to run.
25
PID control pause
Temporal PID invalid and the VFD will output at the current
frequency.
26
Traverse pause (stop at the
current frequency)
The VFD will stop at the current output and after canceling the
function, the VFD will continue to traverse run at the current
frequency.
27
Traverse reset (return to the
middle frequency)
The setting frequency of the VFD will come back to the
middle frequency.
28
Counter reset
Counter clear
29
Torque control disabling
The VFD shifts from torque control mode to speed control
mode.
30
ACC/DEC disabling
Ensure the VFD will not be affected by the external signals
(except for the stopping command) and keep the current
output frequency.
31
Counter trigging
Enable the pulse counter.
32
Length reset
Length counter clear