GD310-UL series VFD
Basic operation instruction
-154-
Set
value
Function
Instructions
4
Jogging
Output ON signal when the VFD is jogging and there is frequency
output.
5
VFD fault
Output ON signal when the VFD is in fault
6
FDT1
Please refer to P08.32 and P08.33 for detailed information.
7
FDT2
Please refer to P08.34 and P08.35 for detailed information.
8
Frequency arrival Please refer to P08.36 for detailed information.
9
Zero-speed
running
Output ON signal when the output frequency and given frequency of
the VFD is 0 at the same time.
10
Upper-limit
frequency arrival
Output ON signal when the running frequency of the VFD is the upper
limit frequency.
11
Upper-limit
frequency arrival
Output ON signal when the running frequency of the VFD is the lower
limit frequency.
12
Ready
When the main circuit and the control circuit is established and the
protection function of the VFD is not active. The VFD is in the running
state and it will output ON signal.
13
Pre-exciting
Output ON signal when the VFD is in the pre-exciting state.
14
Overload
pre-alarm
Output ON signal if the VFD is beyond the pre-alarm point. Refer to
P11.08
–P11.10 for the detailed instruction.
15
Underload
pre-alarm
Output ON signal if the VFD is beyond the pre-alarm point. Refer to
P11.11
–P11.12 for the detailed instruction.
16
Simple PLC stage
completion
Output signal if the simple PLC stage is completed.
17
Simple PLC cycle
completion
Output signal if the simple PLC cycle is completed.
18
Set counting arrival
Output ON signal if the detected counting exceeds the set value of
P08.25.
19
Fixed counting
arrival
Output ON signal if the detected counting exceeds the set value of
P08.26.
20
External fault valid Output ON signal if external fault occurs.
21
Length arrival
Output ON signal if the actual detected length exceeds the se length
by P08.19.
22
Running time
arrival
Output ON signal if the accumulative running time of the VFD exceeds
the setting time by P08.27.
23
MODBUS
communication
virtual terminal
output
Output corresponding signal according to the setting value of
MODBUS. Output ON signal if the setting value is 1 and output OFF
signal if the setting value is 0.