GD310-UL series VFD
Basic operation instruction
-125-
Function
code
Name
Description
Default
value
P02.02
Rated frequency of
asynchronous motor 1
0.01Hz
–P00.03 (max frequency)
60.00
P02.04
Rated voltage of
asynchronous motor 1
0
–1200V
Depend on
model
P04.00
Motor 1V/F curve setting
0: Straight line V/F curve; applying to the
constant torque load
1: Multi-dots V/F curve
2: Torque step-down V/F curve (power of 1.3)
3: Torque step-down V/F curve (power of 1.7)
4: Torque step-down V/F curve (power of 2.0)
5: Customized V/F (V/F separation)
0
P04.01
Torque boost of motor 1 0.0%: (automatic)0.1%
–10.0%
0.0%
P04.02 Torque boost close of motor 1 0.0%
–50.0% (rated frequency of motor 1)
20.0%
P04.03
V/F frequency 1 of motor 1 0.00Hz
–P04.05
0.00Hz
P04.04
V/F voltage 1 of motor 1
0.0%
–110.0%
0.0%
P04.05
V/F frequency 2 of motor 1 P04.03
– P04.07
00.00Hz
P04.06
V/F voltage 2 of motor 1
0.0%
–110.0%
0.0%
P04.07
V/F frequency 3 of motor 1 P04.05
–P02.02 or P04.05–P02.16
00.00Hz
P04.08
V/F voltage 3 of motor 1
0.0%
–110.0%
0.0%
P04.09
V/F slip compensation gain
of motor 1
0.0
–200.0%
100.0%
P04.10
Vibration control factor at low
frequency of motor 1
0
–100
10
P04.11
Vibration control factor at
high frequency of motor 1
0
–100
10
P04.12
Vibration control threshold of
motor 1
0.00Hz
–P00.03 (the max frequency)
30.00 Hz
P04.13
Motor 2 V/F curve setting
0: Straight line V/F curve; applying to the
constant torque load
1: Multi-dots V/F curve
2: Torque step-down V/F curve (power of 1.3)
3: Torque step-down V/F curve (power of 1.7)
4: Torque step-down V/F curve (power of 2.0)
5: Customized V/F (V/F separation)
0
P04.14
Torque boost of motor 2 0.0%: (automatic) 0.1%
–10.0%
0.0%
P04.15 Torque boost close of motor 2 0.0%
–50.0% (rated frequency of motor 1)
20.0%
P04.16
V/F frequency 1 of motor 2 0.00Hz
–P04.05
0.00Hz
P04.17
V/F voltage 1 of motor 2
0.0%
–110.0%
0.0%