GD310-UL series VFD
Function parameter
-90-
Function
code
Name
Description
Default
value
Modify
range of PID adjustor is the max frequency (ignoring
integral and differential function).
The setting range: 0.00
–100.00
P09.05
Integral time
(Ti)
This parameter determines the speed of PID adjustor
to carry out integral adjustment on the deviation of
PID feedback and reference.
When the deviation of PID feedback and reference is
100%, the integral adjustor works continuously after
the time (ignoring the proportional effect and
differential effect) to achieve the max Frequency
(P00.03) or the max Voltage (P04.31). Shorter the
integral time, stronger is the adjustment.
Setting range: 0.00
–10.00s
0.10s
○
P09.06
Differential
time (Td)
This parameter determines the strength of the
change ratio when PID adjustor carries out integral
adjustment on the deviation of PID feedback and
reference.
If the PID feedback changes 100% during the time,
the adjustment of integral adjustor (ignoring the
proportional effect and differential effect) is the max
Frequency (P00.03) or the max Voltage (P04.31).
Longer the integral time, stronger is the adjusting.
Setting range: 0.00
–10.00s
0.00s
○
P09.07
Sampling
cycle (T)
This parameter means the sampling cycle of the
feedback. The adjustor operates each sampling
cycle. The longer the sapling cycle is, the slower the
response is.
Setting range: 0.000
–10.000s
0.100s
○
P09.08
PID control
deviation limit
The output of PID system is the maximum deviation
relative to close loop reference. As shown in the
diagram below, PID adjustor stops to work during the
deviation limit. Set the function properly to adjust the
accuracy and stability of the system.
0.0%
○