GD310-UL series VFD
Expansion card
-220-
Bit
Name
Value
State/Description
14
Dc brake
1
DC braking enable
0
DC braking disable
15
Heartbeat ref
1
Heartbeat enable
0
Heartbeat disable
Reference value (REF):
From 2
nd
word to 12
th
of PZD task message is the main set value REF, main frequency set value is
offered by main setting signal source. As PWM rectifier feedback part doesn
’t have main frequency
setting part, corresponding settings belong to reserved part, the following table shows VFD part
settings for Goodrive310-UL.
Bit
Name
Function
selection
PZD2 receiving 0: Invalid
1: Set frequency (0
–Fmax (unit: 0.01Hz))
2: Given PID, range (0
–1000, 1000 corresponds to 100.0%)
3: PID feedback, range (0
–1000, 1000 corresponds to 100.0%)
4: Torque set value (-3000
–3000, 1000 corresponds to 100.0% the
rated current of the motor)
5: Set value of the forward rotation upper-limit frequency (0
–Fmax
unit: 0.01Hz))
6: Set value of the reversed rotation upper-limit frequency (0
–Fmax
(unit: 0.01Hz))
7: Electromotion torque upper limit (0
–3000, 1000 corresponds to
100.0%of the rated current of the motor)
8: Braking torque upper limit (0
–2000, 1000 corresponds to
100.0% of the rated current of the motor)
9: Virtual input terminals command
Range: 0x000
–0x1FF
10: Virtual output terminals command
Range: 0x00
–0x0F
11: Voltage setting value (special for V/F separation) (0
–1000,
1000 corresponds to 100.0% the rated voltage of the motor)
12: AO output set value 1
(-1000
–1000, 1000 corresponds to 100.0%)
13: AO output set value 2
(-1000
–1000, 1000 corresponds to 100.0%)
0
PZD3 receiving
0
PZD4 receiving
0
PZD5 receiving
0
PZD6 receiving
0
PZD7 receiving
0
PZD8 receiving
0
PZD9 receiving
0
PZD10 receiving
0
PZD11 receiving
0
PZD12 receiving
0
Содержание GD310-011P-4-UL