GD310-UL series VFD
Function parameter
-96-
Function
code
Name
Description
Default
value
Modify
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds:
0: Disable hardware input phase loss protection
1: Enable hardware input phase loss protection
P11.01
Frequency-de
creasing at
sudden power
loss
0: Enable
1: Disable
0
○
P11.02
Frequency
decreasing
ratio at sudden
power loss
Setting range: 0.00Hz/s
–P00.03 (the max frequency)
After the power loss of the grid, the bus voltage
drops to the sudden frequency-decreasing point, the
VFD begin to decrease the running frequency at
P11.02, to make the VFD generate power again. The
returning power can maintain the bus voltage to
ensure a rated running of the VFD until the recovery
of power.
Voltage degree
220V
460V
575V
Frequency-decre
asing threshold
260V
530V
700V
Note
:
1. Adjust the parameter properly to avoid the
stopping caused by VFD protection during the
switching of the grid.
2. Prohibition of input phase protection can enable
this function.
10.00Hz/
s
○
P11.03
Overvoltage
stall protection
0: Disable
1: Enable
DC bus voltage
Overvoltage stall
point
Output frequency
1
○
P11.04
Voltage
protection of
overvoltage
stall
110
–150% (standard bus voltage) (220V)
120%
○
120
–150% (standard bus voltage) (460V)
136%
120
–150% (standard bus voltage) (575V)
120%