GD310-UL series VFD
Product Overview
-10-
Function
Specification
Others
Mountable method Wall and flange mounting
Temperature of the
running environment
-10
–50°C, derate 1% for every additional 1°C above 40°C
Average non-fault time 2 years (25°C ambient temperature)
Cooling
Air-cooling
Braking unit
Built-in for VFDs of 220V(
≤15kW) and 460V(G-type≤30kW,
P-
type≤37kW),
optional for VFDs of 220V(18.5
–55kW) , 460V(G-type≥37kW,
P-type
≥45kW), and 575V
EMC filter
The VFDs of 460V have built-in C3 filters: meet the degree
requirement of IEC61800-3 C3
Overvoltage category
For input voltage 220-240V: transient surge suppression shall
be installed on the line side of this equipment and shall be
rated 220V (phase to ground), 220V (phase to phase), suitable
for overvoltage category
Ⅲ
, and shall provide protection for a
rated impulse withstand voltage peak of 4kV.
For input voltage 323-480V: transient surge suppression shall
be installed on the line side of this equipment and shall be
rated 480V (phase to ground), 480V (phase to phase), suitable
for overvoltage category
Ⅲ
, and shall provide protection for a
rated impulse withstand voltage peak of 6kV.
For input voltage 323-480V: transient surge suppression shall
be installed on the line side of this equipment and shall be
rated 575V (phase to ground), 575V (phase to phase), suitable
for overvoltage category
Ⅲ
, and shall provide protection for a
rated impulse withstand voltage peak of 6kV.
3.4 Name plate
Model:
GD310-022G-4-UL
Power(Output):
22kW
Input:
AC 3PH 380V-480V 56A 47Hz-63Hz
Output:
AC 3PH 0V-Uinput 45A 0Hz-400Hz
S/N:
Made in China
Shenzhen INVT Electric Co.,Ltd
E364851
Figure 3-4 Name plate