GD310-UL series VFD
Communication protocol
-207-
The command sent by the master:
Parameters
address
CRC check
VFD
address
Write
command
Forward
running
If the operation is success, the response may be as below (the same with the command sent by the
master):
Parameters
address
CRC check
VFD
address
Write
command
Forward
running
Set the max Output frequency of the VFD with the address of 03H as100Hz.
Function
code
Name
Description
Setting
range
Default
value
Modify
P00.03
Max. output
frequency
Setting range:
P00.04
–400.00Hz (400.00Hz)
10.00
–400.00 60.00Hz
◎
See the figures behind the radix point, the fieldbus ratio value of the max output frequency (P00.03) is
100. 100Hz timed by 100 is 10000 and the corresponding hex is 2710H.
The command sent by the master:
Parameters
address
VFD
address
Write
command
CRC check
Parameters
data
If the operation is successful, the response may be as below (the same with the command sent by the
master):
Parameters
address
VFD
address
Write
command
CRC check
Parameters
data
Note:
the blank in the above command is for illustration. The blank cannot be added in the actual
application unless the upper monitor can remove the blank by themselves.
10.4.8.3 Example of continuous writing command 10H
Example 1: make the VFD whose address is 01H run forward at 10Hz. Refer to the instruction of
2000H and 0001. Set the address of
“communication setting frequency” is 2001H and 10Hz
corresponds to 03E8H. See the table below.
Function
instruction
Address
definition
Data meaning instruction
R/W
attribute
Communication
control command
2000H
0001H: forward running
R/W
0002H: reverse running
0003H: forward jogging
Содержание GD310-011P-4-UL