GD310-UL series VFD
Basic operation instruction
-129-
Function
code
Name
Description
Default
value
P03.16
Keypad setting for
upper frequency of
forward rotation
0.00Hz
–P00.03 (the max frequency)
60.00 Hz
P03.17
Keypad setting for
upper frequency of
reverse rotation
0.00 Hz
–P00.03 (the max frequency)
60.00 Hz
P03.18
Upper electromotion
torque source
0: Keypad setting upper-limit frequency (P03.20
sets P03.18, P03.21 sets P03.19)
1: AI1
2: AI2
3: AI3
4: HDI
5: MODBUS communication
6: PROFIBUS/CANopen communication
7: Ethernet communication
8: Reserved
Note
: setting mode 1
–4, 100% corresponds to
three times of the motor current.
0
P03.19
Upper braking torque
source
0
P03.20
Keypad setting of
electromotion torque
0.0
–300.0% (rated motor current)
180.0%
P03.21
Keypad setting of
braking torque
0.0
–300.0% (rated motor current)
180.0%
P17.09
Output torque
-250.0
–250.0%
0.0%
P17.15
Torque reference -300.0
–300.0% (rated current of the motor)
0.0%
7.6 Parameters of the motor
Physical accident may occur if the motor starts up suddenly during autotune.
Please check the safety of surrounding environment of the motor and the load
before autotune.
The power is still applied even the motor stops running during static autotune.
Please do not touch the motor until the autotune is completed, otherwise there
would be electric shock.
Do not carry out the rotation autotune if the motor is coupled with the load,
please do not operate on the rotation autotune. Otherwise, misacts or damage
may occur to the VFD or the mechanical devices. When carry out autotune on
the motor which is coupled with load, the motor parameter won
’t be counted
correctly and misacts may occur. It is proper to de-couple the motor from the
load during autotune when necessary.