GD310-UL series VFD
Fault tracking
-176-
Fault
code
Fault type
Cause
Solution
UPE
[27] Parameter
uploading fault
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
and affected by strong
interference.
Communication fault.
Check the keypad wires and
ensure whether there is mistake.
Change the hardware and ask for
service.
Change the hardware and ask for
service.
DNE
[28] Parameter
downloading
fault
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
and affected by strong
interference.
There is mistake on the data
storage of the keypad.
Check the keypad wires and
ensure whether there is mistake.
Change the hardware and ask for
service.
Repack-up the data in the
keypad.
E-DP
[29] PROFIBUS
communication
fault
Communication address is
not correct.
Corresponding resistor is
not dialed
The files of main stop GSD
does not set sound
Check related setting
E-NET
[30] Ethernet
communication
fault
The Ethernet address is not
set right.
The Ethernet
communication is not
selected to right.
The ambient interference is
too strong.
Check the related setting. Check
the communication method
selection.
Check the environment and avoid
the interference.
E-CAN
[31] CANopen
communication
fault
The connection is not sound
Corresponding resistor is
not dialed
The communication is
uneven
Check the connection
Draw out the correspond resistor
Set the same baud rate
ETH1
[32] To-ground
short-circuit
fault 1
The output of the VFD is
short circuited with the
ground.
There is fault in the current
detection circuit.
Check if the connection of the
motor is normal or not
Change the hall
Change the main control panel