GD310-UL series VFD
Basic operation instruction
-136-
Function
code
Name
Description
Default value
P00.11
ACC time 1
0.0
–3600.0s
Depend on model
P00.12
DEC time 1
0.0
–3600.0s
Depend on model
P01.00
Start mode
0: Start-up directly
1: Start-up after DC braking
2: Start-up after rotation speed
tracking 1
0
P01.01
Starting frequency of direct
start
0.00
–50.00Hz
0.50Hz
P01.02
Retention time of the
starting frequency
0.0
–50.0s
0.0s
P01.03
The braking current before
starting
0.0
–100.0%
0.0%
P01.04
The braking time before
starting
0.00
–50.00s
0.00s
P01.05
ACC/DEC selection
0: Linear type
1: Reserved
0
P01.08
Stop mode
0: Decelerate to stop
1: Coast to stop
0
P01.09
Starting frequency of DC
braking
0.00Hz
–P00.03 (the max frequency)
0.00Hz
P01.10 Waiting time of DC braking 0.00
–50.00s
0.00s
P01.11
DC braking current
0.0
–100.0%
0.0%
P01.12
DC braking time
0.00
–50.00s
0.00s
P01.13
Dead time of FWD/REV
rotation
0.0
–3600.0s
0.0s
P01.14
Shifting between
FWD/REV rotation
Set the threshold point of the VFD:
0: Switch after 0 frequency
1: Switch after the starting frequency
2: Switch after the speed reach
P01.15 and delay for P01.24
0
P01.15
Stopping speed
0.00
–100.00Hz
0.50 Hz
P01.16
Detection of stopping
speed
0: Speed setting (the only detection
method in SVPWM mode)
1: Speed detecting value
1
P01.18
Terminal
running protection when
powering on
0: The terminal running command is
invalid when powering on
1: The terminal running command is
valid when powering on
0
Содержание GD310-011P-4-UL
Страница 1: ......
Страница 269: ...6 6 0 0 1 0 0 3 9 3 ...