GD310-UL series VFD
Function parameter
-71-
Function
code
Name
Description
Default
value
Modify
1: Open collector pole output. See P06.02 for
detailed information of the related functions.
P06.01
Y1 output 0: Invalid
1: In operation
2: Forward rotation operation
3: Reverse rotation operation
4: Jogging operation
5: The VFD fault
6: Frequency degree test FDT1
7: Frequency degree test FDT2
8: Frequency arrival
9: Zero speed running
10: Upper limit frequency arrival
11: Lower limit frequency arrival
12: Ready for operation
13: Pre-magnetizing
14: Overload pre-alarm
15: Underload pre-alarm
16: Completion of simple PLC stage
17: Completion of simple PLC cycle
18: Setting count value arrival
19: Defined count value arrival
20: External fault valid
21: Length arrival
22: Running time arrival
23: MODBUS communication virtual terminals output
24: PROFIBUS/CANopen communication virtual
terminals output
25: Ethernet communication virtual terminals output
26: Voltage establishment finished
27
–30: Reserved
0
○
P06.02
HDO output
0
○
P06.03
Relay RO1
output
1
○
P06.04
Relay RO2
output
5
○
P06.05
Polarity of
output
terminals
The function code is used to set the pole of the
output terminal.
When the current bit is set to 0, input terminal is
positive.
When the current bit is set to 1, input terminal is
negative.
BIT0
BIT1
BIT2
BIT3
Y
HDO
RO1
RO2
Setting range: 00
–0F
00
○