GD310-UL series VFD
Function parameter
-84-
Function
code
Name
Description
Default
value
Modify
LED tens: shifting enabling in operation
0: Disabled
1: Enabled
0x00
–0x14
P08.32
FDT1
electrical level
detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical level, the
multi-function digital output terminals will output the
signal of “frequency level detect FDT” until the output
frequency decreases to a value lower than (FDT
electrical level
—FDT retention detection value) the
corresponding frequency, the signal is invalid. Below
is the wave form diagram:
Y
RO1, RO2
,
Output frequency
FDT level
Lag
T
T
Setting range of P08.32: 0.00Hz
–P00.03 (the max
frequency)
Setting range of P08.33: 0.0
–100.0% (FDT1
electrical level)
Setting range of P08.34: 0.00Hz
–P00.03 (the max
frequency)
Setting range of P08.35: 0.0
–100.0% (FDT2
electrical level)
60.00Hz
○
P08.33
FDT1
retention
detection
value
5.0%
○
P08.34
FDT2
electrical level
detection
value
60.00Hz
○
P08.35
FDT2
retention
detection
value
5.0%
○
P08.36
Amplitude
value for
frequency
arrival
detection
When the output frequency is among the positive or
negative detection range of the set frequency, the
multi-function digital output terminal will output the
signal of “frequency arrival”, see the diagram below
for detailed information:
0.00Hz
○