GD310-UL series VFD
Function parameter
-40-
Function
code
Name
Description
Default
value
Modify
1: Terminal running command channel
(“LOCAL/REMOT” flickering)
Carry out the running command control by the
forward rotation, reverse rotation and forward jogging
and reverse jogging of the multi-function terminals
2: Communication running command channel
(“LOCAL/REMOT” on);
The running command is controlled by the upper
monitor via communication
P00.02
Communicatio
n running
commands
Select the controlling communication command
channel of the VFD.
0: MODBUS communication channel
1: PROFIBUS/CANopen communication channel
2: Ethernet communication channel
3: Reserved
Note
: 1, 2 and 3 are extended functions which need
corresponding expansion cards.
0
○
P00.03
Max. output
frequency
This parameter is used to set the maximum output
frequency of the VFD. Users should pay attention to
this parameter because it is the foundation of the
frequency setting and the speed of acceleration and
deceleration.
Setting range: P00.04
–400.00Hz
60.00Hz
◎
P00.04
Upper limit of
the running
frequency
The upper limit of the running frequency is the upper
limit of the output frequency of the VFD which is
lower than or equal to the maximum frequency.
Setting range: P00.05
–P00.03 (Max. output
frequency)
60.00Hz
◎
P00.05
Lower limit of
the running
frequency
The lower limit of the running frequency is that of the
output frequency of the VFD.
The VFD runs at the lower limit frequency if the set
frequency is lower than the lower limit one.
Note
:
Max. output frequency
≥ Upper limit frequency
≥ Lower limit frequency
Setting range: 0.00Hz
–P00.04 (Upper limit of the
running frequency)
0.00Hz
◎
P00.06
A frequency
command
0: Keypad
Modify the value P00.10 (set the frequency by
0
○