7.11 Digital input
Goodrive310-UL series VFDs have 8 programmable digital input terminals and 1 open circuit
electrode output terminal in the standard configuration. All functions of the digital input terminals are
programmable by the function codes. Open collector pole input can be selected into high speed pulse
input terminal or common switch input terminal by function code. When selected into HDI, the user
can select HDI high speed pulse input as frequency given, counting input or length pulse input by
setting.
S1
S2
S3
S4
S5
S6
S7
S8
HD1
P05.10
P05.01
P05.02
P05.03
P05.04
P05.05
P05.06
P05.07
P05.08
P05.09
T delay
T delay
T delay
T delay
T delay
T delay
T delay
T delay
T delay
P05.15
P05.17
P05.19
P05.21
P05.23
P05.25
P05.27
P05.29
P05.31
0
1
2
3
4
5
.
.
.
.
29
30
P05.11
(default value is 1)
(default value is 4)
(default value is 7)
(default value is 0)
(default value is 0)
(default value is 0)
(default value is 0)
(default value is 0)
(default value is 0)
P05.00
0
1
0
1 -1
0
1 -1
0
1 -1
0
1 -1
0
1 -1
0
1 -1
0
1 -1
0
1 -1
0
1 -1
P17.12
Digital input
terminals state
0
No function
1
Forward running
4
Forward jogging
5
Reverse jogging
8
Running pause
9
External fault input
12
Frequency increasing/decreasing
setting clear
13
Shifting between A frequency and
B frequency
16
Multi-stage speed terminal 1
17
Multi-stage speed terminal 2
20
Multi-stage speed pause
21
ACC/DEC time selection 1
2
Reverse running
6
Coast to stop
10
Frequency setting increasing (UP)
14
Shifting between the combination
setting and A frequency
18
Multi-stage speed terminal 3
22
ACC/DEC time selection 2
23
Simple PLC pause
25
PID control pause
28
Counter reset
29
Torque control disabling
26
Traverse pause (stop at the current
frequency)
30
ACC/DEC disabling
32
Length reset
33
Frequency increasing/decreasing
setting clear
34
DC braking
3
3-wire running control
7
Fault reset
11
Frequency setting decreasing (DOWN)
15
Shifting between the combination setting
and B frequency
19
Multi-stage speed terminal 4
23
Simple PLC stopping reset
27
Traverse reset (stop at the middle
frequency)
31
Counter trigging
35
Shift from motor 1 to motor 2
36
Shift the command to the keypad
37
Shift the command to the terminal
38
Shift the command to the
communication
39
Pre-exciting command
40
Power consumption clear
41
Power consumption keeping
42~63
Reserved
P07.39
Input terminals
state at present
fault
Fault?
S1
BIT0
S2
BIT1
S3
BIT2
S4
BIT3
S5
BIT4
S6
BIT5
S7
BIT6
S8
BIT7
HDI
BIT8
P05.10, P17.12, P07.39 display
P05.00
0: HDI is high speed pulse
input
1: HDI is switch input
Fault
Running
Switch function selection
T delay
T delay
T delay
T delay
T delay
T delay
T delay
T delay
T delay
P05.14
P05.16
P05.18
P05.20
P05.22
P05.24
P05.26
P05.28
P05.30
This parameter is used to set the function corresponds to the digital multi-function terminals.
Note
: two different multi-function terminals cannot be set as one function.
Set
value
Function
Instructions
0
No function
The VFD does not work even there is input signal. It is
necessary to set the terminal which cannot be used to
non-function to avoid misacting.
1
Forward running (FWD)
The forward or reverse rotation of the VFD can be controlled
by the external terminals.
2
Reverse running (REV)
3
3-wire running control
The terminal can determine the running mode of the VFD is
3-wire control mode. Refer to P05.13 for detailed instruction
of 3-wire control mode.