GD310-UL series VFD
Basic operation instruction
-164-
Function
code
Name
Description
Default
value
6: MODBUS communication set
7: PROFIBUS/CANopen communication set
8: Ethernet communication set
9: Reserved
P09.01
Keypad PID preset -100.0%
–100.0%
0.0%
P09.02
PID feedback source
0: AI1
1: AI2
2: AI3
3: HDI
4: MODBUS communication feedback
5: PROFIBUS/CANopen communication feedback
6: Ethernet communication feedback
7: Reserve
0
P09.03
PID output feature
0: PID output is positive
1: PID output is negative
0
P09.04
Proportional gain (Kp) 0.00
–100.00
1.00
P09.05
Integral time (Ti)
0.00
–10.00s
0.10s
P09.06
Differential time (Td)
0.00
–10.00s
0.00s
P09.07
Sampling cycle (T) 0.000
–10.000s
0.100s
P09.08
PID control deviation
limit
0.0
–100.0%
0.0%
P09.09
Output upper limit of
PID
P09.10
–100.0% (max frequency or max voltage)
100.0%
P09.10 Output lower limit of PID -100.0%
–P09.09 (max frequency or max voltage)
0.0%
P09.11
Detection value of
feedback offline
0.0
–100.0%
0.0%
P09.12
Detection time of
feedback offline
0.0
–3600.0s
1.0s
P09.13
PID adjustment
0x0000
–0x1111
LED ones:
0: Keep on integral adjustment when the frequency
achieves the upper and low limit; the integration
shows the change between the reference and the
feedback unless it reaches the internal integral limit.
When the trend between the reference and the
feedback changes, it needs more time to offset the
impact of continuous working and the integration
will change with the trend.
0x0001