GD310-UL series VFD
Fault tracking
-174-
Fault
code
Fault type
Cause
Solution
OL2
[12] VFD
overload
The acceleration is too fast
Reset the rotating motor
The voltage of the power
supply is too low.
The load is too heavy.
Close loop vector control,
reverse direction of the
code panel and long
low-speed operation
Increase the ACC time
Avoid the restarting after
stopping.
Check the power of the supply
line
Select a VFD with bigger power.
Select a proper motor.
SPI
[13] Phase loss
on input side
Phase loss or fluctuation of
input R, S, T
Check input power
Check installation distribution
SPO
[14] Phase loss
on output side
U, V, W phase loss input (or
serious asymmetrical three
phase of the load)
Check the output distribution
Check the motor and cable
OH1
[15] Rectifier
module
overheat
Air duct jam or fan damage
Ambient temperature is too
high.
The time of overload
running is too long.
Refer to the overcurrent solution
Redistribute dredge the wind
channel or change the fan
Low the ambient temperature
Check and reconnect
Change the power
Change the power unit
Change the main control panel
OH2
[16] Inverter
module
overheat
EF
[17] External
fault
SI external fault input
terminals action
Check the external device input
CE
[18] 485
communication
fault
The baud rate setting is
incorrect.
Fault occurs to the
communication wiring.
The communication
address is wrong.
There is strong interference
to the communication.
Set proper baud rate
Check the communication
connection distribution
Set proper communication
address.
Chang or replace the connection
distribution or improve the
anti-interference capability.
ItE
[19] Current
detection fault
The connection of the
control board is not good
Assistant power is bad
Hall components is broken
The modifying circuit is
abnormal.
Check the connector and re-plug
Change the hall
Change the main control panel
Содержание GD310-011P-4-UL