GD310-UL series VFD
Expansion card
-224-
Response label (From slave to master)
Confirmation
Function
6: The task could not be implemented due to operational state
7: Request isn’t supported.
8: Request can’t be completed due to communication error
9: Fault occurs when write operation to stationary store
10: Request fails due to timeout
11: Parameter cannot be assigned to PZD
12: Control word bit can’t be allocated
13: Other errors
4
No parameter change rights
Example 1:
Read parameter value
Read keypad set frequency value (the address of keypad set frequency is 10) which can be achieved
by setting PKW1 as 1, PKW2 as 10, return value is in PKW4.
Request (From master to VFD):
PKW1
00
01
PKW2
00
10
PKW3
00
00
PKW4
00
00
CW
xx
xx
PZD2
xx
xx
PZD3
xx
xx
PZD12
xx
xx
CW
Request
...
...
0010: Parameter address
0001: Request for reading parameter values
Response (From VFD to master)
PKW1
00
01
PKW2
00
10
PKW3
00
00
PKW4
50
00
CW
xx
xx
PZD2
xx
xx
PZD3
xx
xx
PZD12
xx
xx
CW
Response
...
...
5000: Parameter value of address 10
0001: Response (parameter values refreshed)
Example 2:
Modify the parameter values (RAM and EEPROM are modified)
Modify keypad settings frequency value (the address of keypad set frequency is 4) which can be
achieved by setting PKW1 as 4; PKW2 as 10, modification value (50.00) is in PKW4.
Request (From master to VFD):
PKW1
00
04
PKW2
00
10
PKW3
00
00
PKW4
50
00
CW
xx
xx
PZD2
xx
xx
PZD3
xx
xx
PZD12
xx
xx
CW
Request
...
...
0004: Parameter changes
5000: Parameter value of address 10