GD310-UL series VFD
Basic operation instruction
-146-
Function
code
Name
Description
Default
value
13: High speed pulse HDI input value
14: MODBUS communication set value 1
15: MODBUS communication set value 2
16: PROFIBUS/CANopen communication
set value 1
17: PROFIBUS/CANopen communication
set value 2
18: Ethernet communication set value 1
19: Ethernet communication set value 2
20
–21: Reserved
22: Torque current (relative to the rated
current of the motor)
23: Pre-magnetizing current (relative to the
rated current of the motor)
24
–30: Reserved
P06.17
Lower output limit of AO1 -100.0%
–P06.19
0.0%
P06.18
Corresponding AO1
output of lower limit
0.00V
–10.00V
0.00V
P06.19
Upper output limit of AO1 P06.17
–100.0%
100.0%
P06.20
The corresponding AO1
output of upper limit
0.00V
–10.00V
10.00V
P06.21
AO1 output filter time
0.000s
–10.000s
0.000s
P06.22
Lower output limit of AO2 -100.0%
–P06.24
0.0%
P06.23
Corresponding AO2
output of lower limit
0.00V
–10.00V
0.00V
P06.24
Upper output limit of AO2 P06.22
–100.0%
100.0%
P06.25
The corresponding AO2
output of upper limit
0.00V
–10.00V
10.00V
P06.26
AO2 output filter time
0.000s
–10.000s
0.000s
P06.27
Lower output limit of HDO -100.0%
–P06.29
0.00%
P06.28
Corresponding HDO
output of lower limit
0.00
–50.00kHz
0.0kHz
P06.29
Upper output limit of HDO P06.27
–100.0%
100.0%
P06.30
Corresponding HDO
output of upper limit
0.00
–50.00kHz
50.00kHz
P06.31
HDO output filter time
0.000s
–10.000s
0.000s