GD310-UL series VFD
Function parameter
-95-
Function
code
Name
Description
Default
value
Modify
P10.35
BIT1
BIT0
8
00
01
10
11
BIT3
BIT2
9
00
01
10
11
BIT5
BIT4
10
00
01
10
11
BIT7
BIT6
11
00
01
10
11
BIT9
BIT8
12
00
01
10
11
BIT11 BIT10 13
00
01
10
11
BIT13 BIT12 14
00
01
10
11
BIT15 BIT14 15
00
01
10
11
After users select the corresponding ACC/DEC time,
the combining 16 binary bit can be changed into
hexadecimal bit, and then set the corresponding
function codes.
ACC/DEC time 1 is set by P00.11 and P00.12;
ACC/DEC time 2 is set by P08.00 and P08.01;
ACC/DEC time 3 is set by P08.02 and P08.03;
ACC/DEC time 4 is set by P08.04 and P08.05.
Setting range: -0x0000
–0xFFFF
P10.36
PLC restart
0: Restart from the first step; stop during running
(caused by the stop command, fault or power loss),
run from the first stage after restart.
1: Continue to run from the stop frequency; stop
during running (caused by stop command and fault),
the VFD will record the running time automatically,
enter into the stage after restart and keep the
remaining running at the setting frequency.
0
◎
P10.37
Multi-step time
unit
0: Seconds; the running time of all steps is counted
by second
1: Minutes; the running time of all steps is counted by
minute
0
◎
P11 Group Protective parameters
Function
code
Name
Description
Default
value
Modify
P11.00
Phase loss
protection
0x00
–0x11
Ones:
0: Disable input phase loss protection
1: Enable input phase loss protection enable
Tens:
11
○