GD310-UL series VFD
Function parameter
-78-
Function
code
Name
Description
Default
value
Modify
P07.15
High bit of
power
consumption
Display the power used by the VFD.
The
power
consumption
of
the
VFD
=P07.15*1000+P07.16
Setting range of P07.15: 0
–65535
kWh (*1000)
Setting range of P07.16: 0.0
–999.9 kWh
●
P07.16
Low bit of
power
consumption
●
P07.17
Reserved Reserved
●
P07.18
Rated power
of the VFD
0.4
–3000.0kW
●
P07.19
Rated voltage
of the VFD
50
–1200V
●
P07.20
Rated current
of the VFD
0.1
–6000.0A
●
P07.21
Factory bar
code 1
0x0000
–0xFFFF
●
P07.22
Factory bar
code 2
0x0000
–0xFFFF
●
P07.23
Factory bar
code 3
0x0000
–0xFFFF
●
P07.24
Factory bar
code 4
0x0000
–0xFFFF
●
P07.25
Factory bar
code 5
0x0000
–0xFFFF
●
P07.26
Factory bar
code 6
0x0000
–0xFFFF
●
P07.27
Type of
present fault
0: No fault
1: IGBT U phase protection (OUt1)
2: IGBT V phase protection (OUt2)
3: IGBT W phase protection (OUt3)
4: Overcurrent during acceleration (OC1)
5: Overcurrent during deceleration (OC2)
6: Overcurrent during constant speed running (OC3)
7: Overvoltage during acceleration (OV1)
8: Overvoltage during deceleration (OV2)
9: Overvoltage during constant speed running (OV3)
10: Bus undervoltage (UV)
11: Motor overload (OL1)
12: VFD overload (OL2)
13: Phase loss on input side (SPI)
●
P07.28
Type of the
last fault
●
P07.29
Type of the
last but one
fault
●
P07.30
Type of the
last but two
fault
●
P07.31
Type of the
last but three
fault
●
Содержание GD310-011P-4-UL
Страница 1: ......
Страница 269: ...6 6 0 0 1 0 0 3 9 3 ...