Quick Start Guide

 

For GVX9000 AF Drives

June 2006
New Information 

00GQ

5011646300

Summary of Contents for GVX9000

Page 1: ...MN04000002E June 2006 Quick Start Guide For GVX9000 AF Drives June 2006 New Information 00GQ 5011646300...

Page 2: ...6 18 15 6 18 15 6 18 15 6 GVX007A1 2 GVX010A1 2 GVX015A1 2 GVX020A1 2 240V 7 1 2 hp 240V 10 hp 240V 15 hp 240V 20 hp 26 25 34 33 50 49 60 65 8 8 4 8 8 4 6 13 3 4 21 2 30 26 0 30 26 0 30 26 0 Use Termi...

Page 3: ...r 0 to 10V DC Factory Setting Analog Frequency Digital Output Factory Setting Warning Digital Output Factory Setting Frequency Setting Indication Factory Setting Fault Indication NC Relay Output Facto...

Page 4: ...4 COM 24V Power Supply Used for Source mode HIGH VOLTAGE Wiring work shall be carried out only by qualified personnel Otherwise there is a danger of electric shock or fire START This button operates a...

Page 5: ...t STOP motor STOP from the panel active control place has to be selected at Panel RESET used to reset an Active Fault on the drive and shown in the display This button switches the Control Location fr...

Page 6: ...is unsuccessful the keypad will display an Invalid Data message the parameter will not be changed and the parameter number will again be displayed Note Some parameters cannot be changed while the unit...

Page 7: ...5H 30 06 A2 Maximum Input Current 0 20 mA 0 00 to 20 00 mA 20 00 mA 0106H 30 07 A2 Minimum Input Current 0 20 mA 0 00 to 20 00 mA 4 00 mA 0107H 30 08 A2 Maximum Output Frequency 400 0 to 400 0 Hz 60 0...

Page 8: ...Remote Local Remote close for remote 15 Increase Master Frequency 16 Decrease Master Frequency 17 Forward Reverse 18 Parameter Lock 19 Acceleration Deceleration Inhibit 20 Run Enable 21 PAUSE NO 22 PA...

Page 9: ...0 Hz 0 00 Hz 012CH 30 45 Preset Speed 15 0 00 to 400 00 Hz 0 00 Hz 012DH 30 46 Display Frequency Hz or Percent 00 Frequency Hz 00 01 Percent 02 User Definition 0 001 max unit Unit set by 30 47 012EH 3...

Page 10: ...g a RUN command 29 Fout Fmin 30 PG Error 31 Low Voltage indication User Defined 32 Inverter RUN command state 33 Brake ON Brake OFF 40 10 40 11 0206H 40 07 Frequency Attained 1 0 00 to 400 00 Hz 0 00...

Page 11: ...Command 03 Operating commands determined by the RS 485 communication interface Keypad STOP key is enabled 00 04 Operating commands determined by the RS 485 communication interface Keypad STOP key is n...

Page 12: ...Series 0 1 to 255V 1 7 460V Series 0 1 to 510V 3 4 575V Series 0 1 to 637V 4 8 0312H 50 19 Minimum Output Frequency 0 00 to 20 00 Hz 1 50 0313H 50 20 Minimum Output Voltage 230V Series 0 1 to 50V 1 7...

Page 13: ...Operation 02 Disable Forward Operation 0329H 50 42 Momentary Power Loss 00 Stop operation after momentary power loss 0 01 Continue operation after momentary power loss speed search from Speed Referen...

Page 14: ...d Continue Operation 0345H 50 70 Sleep Frequency 0 0 Disabled 0 00 0 00 to 400 Hz Enabled 0346H 50 71 Wake Frequency 0 00 to 400 00 Hz 0 00 0347H 50 72 Sleep Time Delay 0 0 to 600 sec 0 0348H 50 73 Fr...

Page 15: ...Feedback Fault Detection Time 0 01 10 00 sec 1 00 0419H 60 26 CLV Encoder Feedback Filter 00 Disable 00 0 002 1 00 041AH 60 27 CLV Encoder Slip Range Deviation Range 0 0 50 0 10 0 041BH 60 28 CLV Enco...

Page 16: ...H 70 16 Low Voltage Detection Time 0 to 3600 0 sec 0 5 0510H 70 17 Cooling Fan Mode 0 Always on 0 1 Fan is off one minute after stop command 2 Fan on with run fan off with stop 3 Fan on when temp limi...

Page 17: ...Fault 25 Feedback Deviation Err 26 Count Attained 0607H 80 08 Power Up Display Selection Also Order of Appearance When Scrolling through Display Modes 00 Command Frequency 00 01 Output Frequency 02 O...

Page 18: ...nal value 10 Display AI1 11 Display AI2 12 Display AI3 13 Unit Temperature 0611H 80 18 Password Input 1 65535 0 0612H 80 19 Password Decode 0 65535 0 Fault Name Fault Descriptions Corrective Actions O...

Page 19: ...Internal electronic overload trip 1 Check for possible motor overload 2 Check electronic thermal overload setting 3 Increase motor capacity 4 Reduce the current level so that the drive output current...

Page 20: ...ilure Return the drive to the factory CPU Failure 3 Drive s internal circuitry is abnormal 1 Switch off power supply 2 Check whether the input voltage falls within the rated AC drive input voltage Swi...