NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
64
The chilled water pipes should be wrapped with thermal insulation foam and the
interspaces of the knock-off holes should be filled with thermal insulation foam.
Pipes can be routed from the bottom or side. Determine the pipe routing method based on
site conditions.
If it is difficult to route pipes or cables through the bottom plate, route them through side
panels. Ensure that pipes and power cables are routed correctly and through separate holes.
Make only the necessary knock-out holes; otherwise, the system performance may be
degraded.
After pipes are routed for the NetCol8000-C, seal the gap between the pipe and the pipe
hole.
To minimize the noise due to device vibration, perform the following operations:
When the routing direction of the chilled water pipe is changed, add a fastener at the
position that is 1000 mm away from the changing point.
When the chilled water pipe is straight, add a fastener every 2500 mm.
Onsite personnel prepare the required materials and install the fasteners.
Figure 3-33
Fastener layout (unit: mm)
Table 3-8
Chilled water pipe port diameter
Unit Model
Inlet Pipe Outer Port
Diameter
Outlet Pipe Outer Port
Diameter
NetCol8000-C
G 2in, connected over screw
threads
G 2in, connected over screw
threads