NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
202
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
enabled.
A026-01
Air filter exceed
runtime alarm
Warning
N/A
The
accumulated
runtime of the
air filter
exceeds the
alarm threshold.
Maintain or
replace the air
filter and clear
the accumulated
runtime.
A027-01
Power loss
alarm
Warning
An alarm is
triggered.
The power
supply is cut
off.
If power failure
occurs on the
power system,
no maintenance
is needed. If it
occurs in other
places, check
the power
supply cables.
A042-01
Remote
shutdown alarm
Major
An alarm is
triggered, and
the smart
cooling product
is shut down.
1.
The remote
shutdown
dry contact
is triggered.
2.
The cables
to the
remote
shutdown
dry contact
are loose or
damaged.
1.
Check the
status of the
remote
shutdown
dry contact.
2.
Check the
cables to the
remote
shutdown
dry contact.
A044-01
Smoke sensor
alarm
Critical
An alarm is
triggered, and
the smart
cooling product
is shut down.
1.
Smoke is
generated in
the
equipment
room.
2.
The cables
to the smoke
sensor are
loose or
damaged.
3.
The smoke
sensor is
faulty.
1.
Expel smoke
from the
equipment
room and
reset the
smoke
sensor.
2.
Check the
cables to the
smoke
sensor.
3.
Maintain or
replace the
smoke
sensor.
A048-01
Supply air high
temperature
alarm
Critical
N/A
1.
The
temperature
sensors or
temperature
and
humidity
sensors are
1.
Adjust the
positions of
the
temperature
sensors or
temperature
and