NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
7 FAQ
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
289
To prevent key data from being lost, you are recommended to record all parameter values or
back up data with export configurations before restoring defaults. Then change the parameter
values back to the recorded values after restoring defaults. For details about how to use export
configurations, see
After default settings are restored, all communication addresses are changed to 1 and the communication
between all devices and the EMS is disconnected. The communication addresses must be reset to
recover the communication.
7.1.18 Exporting Data
Context
With the one-click mode, you can export active alarms, historical alarms, run logs, and so on.
You are advised to use the FAT32 USB flash drive with a capacity no greater than 64 GB.
Format the non-FAT32 USB flash drives into FAT32 ones before using them.
Before using a USB flash drive, ensure that its data has been scanned by antivirus software
and is secure.
Before exporting active alarms, historical alarms, logs, and configurations, ensure that the USB flash
drive has been successfully identified. The USB port is located on the side of the screen.
If the USB flash drive has been successfully identified,
is displayed in the status bar.
If the USB flash drive is not properly connected, the system will display
No USB device found.
during operations about the USB flash drive.
Procedure
Step 1
Tap
Maint
>
USB Operations
>
Export
to enter the
Select Path
screen, as shown in